HF-CS anti-condensation intelligent dehumidification device is widely used in high and low voltage control cabinet, GIS control cabinet, high and low voltage switch cabinet, ring main unit, outdoor terminal box, mechanical control cabinet, box type substation, dry type substation and other small electrical equipment. At the same time, it is also suitable for all kinds of small electrical cabinets with high humidity and high requirements for maintaining humidity. The device monitors the temperature and humidity in real time and operates automatically, which adopts the advanced semiconductor refrigeration technology.
● With highly-integrated CPU and internal electronic components from international manufacturers, the device has high operation stability.
● It has a special air duct design, which can automatically supply air and condense, exhaust gas, and heat and reduce humidity, so that the dehumidification effect can be better.
● With 1-channel relay outlet, it can be connected to the heater in the cabinet, and the automatic start value of heating can be set on the device.
● RS485 sends temperature and humidity information, working status and failure status to the background in real time through MODBUS protocol. The manual working state can be switched to remotely.
● It has the advantages of small volume, lightweight, convenient installation and the shell made of flame retardant material. The starting value of temperature and humidity in automatic state can be set on the device.
● It shall be used inside the cabinet and shall be installed vertically to ensure that condensed water can be discharged through the conduit.
● When installing, ensure that the surrounding of the device is ventilated and free of obstructions, so as not to affect the circulation of the air duct.
● After ordering, the required outlet pipe length and the installation method used on site shall be provided.
Description |
Parameter |
Working power supply |
90 - 500 AC/DC (DC>360, it will close) |
Operating temperature |
0℃~60℃ |
Dehumidification volume |
3m³ ~5m³ |
Overall power consumption |
≤60W, the maximum no more than 72W |
Working humidity |
20%RH~95%RH |
Moisture removal |
400ml/day (at +35℃ and 85%RH) |